| Motor Connecting Cables | |||
| 2YSLCY-JB/2YSLCYK-JB | 9YSLCY-JB | PENDANT CABLE |
Mineral insulated cables
Mineral Insulated Heating Cable,single core up to 480 °C
Application
Moisture proof applications at high outputs and temperatures
High-temperature sistuations
Can be immersed in fluids
Chemical & petrochemical industries
Machinery and plant construction
Molten Salt Applications
Vacuum technology
Heat tracing on piping
Heat tracing on vessels
Standard
EN 60079-30-1
Voltage Rating
500V
CABLE CONSTRUCTION

Conductors: Solid alloy or copper conductor.
Insulation: Magnesium Oxide (MgO).
Outer sheath: Stainless Steel 1.4541 (AISI 321).
Mechanical and Thermal Properties
Maximum Operating temperature: 480℃
Maximum continuous exposure temperature: 600℃
Minimum installation temperature: -60℃
Bending radius: 6×OD
Nominal output: 250 W/m
Cold lead, length: 2 x 0.50 m
Cold lead, cross section: 2.50 mm²
Impact resistance: 7 J
Cable Parameter
Overall Diameter mm |
Resistance at 20 °C |
Temperature coefficient |
|---|---|---|
3.20 |
10000 |
0.09 |
3.20 |
6300 |
0.09 |
3.20 |
4000 |
0.09 |
3.40 |
2500 |
0.09 |
3.60 |
1600 |
0.09 |
3.90 |
1000 |
0.09 |
4.30 |
630 |
0.09 |
4.70 |
400 |
0.09 |
5.30 |
250 |
0.09 |
6.50 |
160 |
0.09 |
Note: The parameters listed above are nominal values as per cable standards. Actual values may vary due to material and manufacturing process variations. For precise specifications or customized requirements, please contact us for further information